| Electromagnetic 
        control components demand inrush currents up to 10 times the transformer's 
        nominal rating. While this inrush is occurring, the output side of the 
        transformer must not fall below 85% of nominal as specified by NEMA St. 
        1, Part 4. Using a transformer that does not meet these ratings may cause 
        erroneous shutdowns or glitches in products downstream. For 
        proper transformer selection, three characteristics of the load circuit 
        must be determined in addition to the minimum voltage required to operate 
        the circuit. These are total steady state (sealed) VA, total inrush VA, 
        and inrush load power factor.   
        A. 
          Total steady state (sealed) VA is the volt-amperes that the 
          transformer must deliver to the load circuit for an extended period 
          of time. B. 
          Total inrush VA is the volt-amperes that the transformer 
          must deliver upon initial energization of the control circuit. Energization 
          of electromagnetic devices takes 30-50 milliseconds. During this inrush 
          period the electromagnetic control devices draw many times normal current 
          - 3-10 times normal is typical. C. 
          Inrush load power factor is difficult to determine without 
          detailed vector analysis of all the load components. Generally such 
          an analysis is not feasible. Therefore, a safe assumption is 40% power 
          factor. Until recently 20% PF was commonly used for transformer selection, 
          however, tests conducted on major brands of control devices indicate 
          that 40% PF is more accurate. Selection 
        
           
            Determine the supply and load voltages as well as your required frequency 
            (i.e. 60Hz). The supply voltage is the available voltage to the control 
            transformer. The load voltage is the operating voltage of the devices 
            that will be connected to the transformer output.
           
            Calculate the total sealed VA by adding the VA requirements of all 
            components that will be energized together (timers, contactors, relays, 
            solenoids, pilot lamps, etc.). Sealed VA data is available from the 
            control device manufacturer.
           
            Add the inrush VA of all components that will be energized together. 
            Be sure to include the sealed VA of components that don't have an 
            inrush, (lamps, timers, etc.) as they present a load to the transformer 
            during maximum inrush.
           
            Calculate selection inrush VA in one of the following two ways: |